不同型號的母線槽進水如何處理

文章來源:http://www.yeeones.com/?? 作者:電纜橋架廠家發布時間:2023-04-07?瀏覽次數:

返回:常見問題
一、高強封閉母線槽進水
1、 High strength enclosed busbar duct water inlet
如果出現高強封閉母線槽進水的情況,無需特殊處理,處理措施是,可以先將水控干,擦干高強封閉母線槽的水分,與此同時,可以檢查槽體內有無異物有異物出現立即打掃干凈,以免發生通電短路事故。
If there is water ingress into the high-strength enclosed busbar duct, there is no need for special treatment. The treatment measure is to first control the water and wipe off the moisture in the high-strength enclosed busbar duct. At the same time, it is possible to check if there are any foreign objects inside the duct and clean it immediately to avoid power on and short circuit accidents.
二、密集型母線槽
2、 Dense busbar duct
密集型母線槽的防護等級,如果防護等級高,有一點水對它沒有太大的傷害,如果防護等級低,必須先把水擦拭干凈,否則會出現短路。保護級別可以看IP數,若是IP的數值越大,則表示其防塵防水的能力越強。
The protection level of dense bus duct is high. If the protection level is high, a little water will not cause much harm to it. If the protection level is low, the water must be wiped clean first, otherwise a short circuit may occur. The protection level can be determined by the number of IPs. If the IP value is higher, it indicates that its dustproof and waterproof ability is stronger.
若保護等級低,可直接找廠家,每節母線測試相間及相間外殼電阻,若是一節不在規定范圍內,都必須更換,因為不好烘干,更換價格估計是原來母線槽價的30%-40%。
If the protection level is low, you can directly contact the manufacturer to test the interphase and interphase shell resistance of each busbar section. If one section is not within the specified range, it must be replaced because it is difficult to dry, and the replacement price is estimated to be 30% -40% of the original busbar slot price.
山東電纜橋架
山東電纜橋架廠家提醒,一般設計在室內使用的母線槽,空氣濕度對其運行不會產生影響,但使用時進水,勢必導致絕緣降低,長時間運行會造成短路,燒毀母線槽。所以對可能引起母線槽進水的安裝方式應采取防護措施。
The manufacturer of cable tray in Shandong reminded that the air humidity of the bus duct generally designed for indoor use will not affect its operation, but water ingress during use will inevitably lead to insulation reduction, and long-term operation will cause short circuit and burn the bus duct. Therefore, protective measures should be taken for installation methods that may cause water ingress into the busbar duct.
當母線槽穿越樓層時,由于生產或屋面滲漏等各種原因導致樓層積水,便會沿穿越樓層的母線槽漏出,導致母線槽進水,從而降低了母線槽絕緣。
When the bus duct passes through a floor, due to various reasons such as production or roof leakage, water accumulates in the floor, leading to leakage along the bus duct that passes through the floor, causing water to enter the bus duct and reducing its insulation.
遇到母線槽進水情況的時候,業主應該聯系專業的人員并且告知目前的情況,人員應當在現場尋找漏水問題,全面檢查,并把已進水或已燒壞的母線槽進行拆卸返回工廠檢修,根據情況是否更換材料。您對此有什么疑惑或需求就來我們網站http://www.yeeones.com咨詢吧!
When encountering water ingress into the busbar duct, the owner should contact professional personnel and inform them of the current situation. The personnel should search for the leakage problem on site, conduct a comprehensive inspection, and dismantle the busbar duct that has been flooded or burnt out and return it to the factory for maintenance. Depending on the situation, materials should be replaced. If you have any doubts or needs about this, please come to our website http://www.yeeones.com Consult!